ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048
Page 34
> C12/2
SENSOR MENU
(Cn/m) Change Item n To Value m (Jn) Jump To Record n
(A) Insert After This Record (N) Go To Next Record
(B) Insert Before This Record (P) Go To Previous Record
(X) Cut Record to Clipboard (XA) Delete ALL Records
(C) Copy Record To Clipboard (Z) Zeno Program Menu
(V) Paste Record From Clipboard (H) Help
(Sn/m) Search Item n for Value m
Sensor Items for Record 1 of 1:
Item 1: Sensor Type Code 1 (12-bit Analog to Digital)
Item 2: Sensor Name IntTemp
Item 3: Sensor Input Channel INTERNAL TEMPERATURE SENSOR
Item 6: Switched Power Code 0 (NO SWITCHED POWER)
Item 7: Sensor Excitation Voltage Code 0 (NO EXCITATION VOLTAGE)
Item 8: Switched Excitation Return 0
Item 9: Switched Power Warmup Time 0
Item 10: Sensor Sample Count 1
Item 11: Maximum Sensor Readings 0
Item 12: Sensor Timing Loop 2 (1.0 seconds)
Item 13: Conversion Coefficient A 0
Item 14: Conversion Coefficient B 1
Item 15: Conversion Coefficient C 0
Item 17: No. of Additional 15-msec Delays 0
>
The Sensor Type Definition for our Internal Temperature Sensor is now complete. Creation of this
Sensor Type Definition took four commands. Since the ZENO
®
-3200 supports multiple, space-delimited
commands being sent in a single command line, you could have sent all four commands in this single
command line in the Sensor Menu: C1/1 C2/IntTemp C3/INT C12/2{ENTER}.
One Sensor Record is now fully configured, but for our example, one more Sensor Record needs to be
configured to measure Battery Voltage.
We need to tell the ZENO
®
-3200 to create another Sensor Record. Two commands in the Sensor Menu
are available for this purpose: the "A" and "B" commands. The "A" command instructs ZENOSOFT
®
to
create a new Sensor Record AFTER the current Sensor Record. The "B" command instructs
ZENOSOFT
®
to create a new Sensor Record BEFORE the current Sensor Record.
32
During the Sample Duration, data is collected from sensors based upon the
order of the Sensor Records and the Sensor Timing Loop assigned to each
sensor.
From our example configuration, we want the Sensor Record for Battery Voltage to come after the
Internal Temperature Sensor. To create a new Sensor Record after the current one, type the command
A{ENTER} in the Sensor Menu and the screen will look like the following:
32
This is also discussed in Section 10.2.