ZENO®-3200 User Manual Version V2.02 June 27, 2003 P/N: 0302116012, Revision C Michael J. Hart (Software Engineer) COASTAL ENVIRONMENTA
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 2 What each sensor is. When to collect the data from each sensor.
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 92Configuring and using the UDP PAD service requires familiarity with
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 93Forwarding a CDPD Packet The cellular modem closes and sends a packe
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 94Type AT+WPNEI=aaa.aaa.aaa.aaa{ENTER} where aaa.aaa.aaa.aaa is the TC
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 95The ZENO®-3200 radio and your host must have good Line of Site (LOS)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 96Auxiliary Port Pin Pin Function 4 Push-To-Talk (PTT) 9 Audio Transm
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 97is to be used to control radio power in the Power Control Menu. To
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 98 DIGITAL CONTROL MENU (Cn/m) Change Item n to Value m (E) Save
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 99You may have to send the U{ENTER} command several times to enter the
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1006.6.7. Data Packetization To ensure that a complete message is sen
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 101Use of the Data Collection System is limited to the collection of e
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 3 Frequency inputs: Up to 100 kHz at 0.005% accuracy. 1.3.3. Sensor
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 102Other lines: (757) 824-0125 (757) 824-0156 (757) 824-0126
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 103 > DOWNLOAD MESSAGE_FILE PLATFORM_CE1192D4 BEGIN DOWNLOAD? (Y/N
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 104 Figure 6-1. Eastern satellite pointing angles (azimuth: broken li
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 105 Figure 6-8. Western satellite pointing angles (azimuth: broken lin
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 106The TGT-1 DE-25 port labeled GOES RADIO is connected to the ZENO®-3
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 107For the Campbell Scientific SAT HDR GOES transmitter, set the COM2
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 108 If you will be using self-timed transmissions, specify the self-
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1096.7.7. Connecting A GOES Radio and Serial Sensors To The Same COM
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 110To define an output message in GOES Binary Format, each field of th
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 111Coastal Environmental Systems uses the Telonics ST-13 ARGOS Platfor
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 4In practice, the best available sample rate is often rather lower tha
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 112Regional Processing Centers (RPC) are located worldwide in the Unit
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 113 COMMUNICATIONS MENU (Cn/m) Change Item n To Value m (Tn) Termina
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 114With the above communications settings, any regular ZENO®-3200 Data
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 115 Terminal Passthrough Mode: direct communication between two ZENO
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 116 COMMUNICATIONS MENU (Cn/m) Change Item n To Value m (R)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1176.9.2. SDI-12 Passthrough Mode The SDI-12 Passthrough Mode lets yo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 118The following example shows how you can use the SDI-12 Passthrough
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 119SYSTEM FUNCTIONS MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 120 The four ASCII characters whose decimal value range between 28 and
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 121 REPEATER MENU (Cn/m) Change Item n To Value m (U) User M
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 52. ZENO®-3200 BASICS Coastal Environmental Systems ZENO®-3200 User
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1221. The ZENO®-3200 receives a CCSAIL message. 2. The ZENO®-3200 ch
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 123 REPEATER MENU (Cn/m) Change Item n To Value m (U) User M
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 124This section describes how to set up the ZENO®-3200 and the speech
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 125 OUTPUT MESSAGE TIMING MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 126 DATA OUTPUT MENU (Cn/m) Change Item n To Value m (Jn)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 127 DATA OUTPUT MENU (Cn/m) Change Item n To Value m (Jn)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 128 MODEM MENU (Cn/m) Change Item n To Value m (Q) Quit (E)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 129If the speech interface is disabled and modem settings are unchange
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 130 Figure 6-11. Speech interface wiring diagram. 6.12. OPTION
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 131The default ZENO®-3200 configuration excludes COM1 and COM2 from th
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 6 Figure 2-1. ZENO®-3200 Front Panel Diagram A
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1327. MONITORING & CALIBRATING SENSOR DATA Coastal Environmental
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 133 For sensors that output more than one data value, only the first v
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 134 TEST MENU (Rx,y) Display Sensors x-y RAW Data (Ex) Displ
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1351. Number of times Sensor Record has been called to collect data.
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 136You will need to thoroughly know the links between each Sensor and
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1377.6. DISPLAYING GLOBAL BUILT-IN-TEST (BIT) STATUS The Global Built
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1388. ZENO®-3200 ACCESS PRIVILEGES Coastal Environmental Systems Z
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 139 ZENO PROGRAM MENU (S) Sensor Menu (M) Memo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 140To change either the Administrator Password or the User Password, y
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1419. UPLOADING AND DOWNLOADING AN ENTIRE CONFIGURATION Coastal Envi
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 72.2. COMMUNICATING WITH AND POWERING UP THE ZENO®-3200 You will need
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 142As with downloading Data Records, you can either download the confi
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 143 X-modem Transfer: Enter XT{ENTER} in the System Load Menu. The
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 144Type n{ENTER} to not accept deletion of all Data Records, and ZENOS
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 145Option V in the System Load Menu allows you to download your config
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 146Custom versions of ZENOSOFT® are distinguished from standard versio
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 14710. ZENO®-3200 CONFIGURATION SPECIFICS Coastal Environmental Sy
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 148configuration changes either to EEPROM or as a file in your compute
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 149 SENSOR MENU (Cn/m) Change Item n To Value m (Jn) Jump
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 150Appendix D contains a number of sensor configuration examples for c
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 151Due to their fine, as opposed to coarse, resolution 18-bit ADC meas
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 84. The ZENO®-3200 requires a power source of 10 to16 VDC. You can e
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 152Contact Coastal Environmental Systems if you need an Analog Expansi
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 15318-bit ADC Input voltage range selection Nominal full scale sensor
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 154 Simple on/off status Period of streaming digital pulses Fr
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 155Sensor Type Code Name Specifics 4 Digital Period Measurement, f
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 156 NMEA 0183: this interface protocol was created by the National M
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 157$HCHDM,342.7,M*2B The value set in the Compass Offset of the System
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 158#00011505<CR><LF>5.65,-24.98,78.2,0,1.2,1A0,51<ETX&g
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 159 Unlike the regular CCSAIL Sensor, no Sensor Input Channel is speci
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 160atttn<CR><LF> where ttt is the time in seconds required
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 161General Serial Script Sensor Specifics (USI) A full explanation of
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 92.3.1. RAM Each ZENO®-3200 is shipped with a minimum of 256 kilobyte
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 162Available Port Types Channel (COM Port) Available Port Types COM1
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 163Sensor Type Code (Line Item #1) Name Available Channels (Line Item
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 164All SDI-12 and CCSAIL sensors are designed to be used where there i
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 165Coastal Environmental Systems recommends that any communications po
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 166 Sample Interval |---------------------------------------| 20s
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 167Coastal Environmental Systems recommends that the period length of
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 168Count. When the Sensor Sample Count is set to one, only one measur
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 169The ZENO®-3200 conserves power by turning on a switched voltage onl
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 170The ZENO®-3200 will turn on a switched voltage before the start of
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 171The ZENO®-3200 sets the Excitation Voltage to the value specified i
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 10Once you are done creating or modifying the configuration, it is rec
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 172If your sensor output is linear192, then coefficient A is always ze
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 173In the case of parabolic (or near-parabolic) sensor outputs, three
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 174the Zeno Program Menu by typing the command P{ENTER}. A Process Re
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 175Category Number (Line Item #1) Process Category Name Description
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 176Process Category Code (Line Item #1) Process Number (Line Item #2)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 177 2 - Add Constant Value 3 - Add Two Data Values 4 - Subtract Tw
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 178The most important resource in knowing which processes you will nee
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 17910.4.5. Process Error Checking and Reporting Sometimes, the ZENO®-3
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 180the received value is out of range, bit 2 will be set in the error
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 181The range for any constant is a floating-point number between 3.40
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 11 Changes to process definitions, including addition or deletion of
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 182A Data Output Record is an individual data field to be transmitted
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 18310.6.2. Output Message Structure Like the Data Record structures, t
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 18410.6.3. The Different Types of Data Output Records Line Item #1 of
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 185Table of Data Output Record Field Type Codes Field Type Code (Line
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 186Detailed Information about Data Output Field Type Codes Field Type
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 187Codes #1 or #2. No characters preceding this point in the message
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 188Instead, you need to specify which Data Output Field Type to use to
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 189The length of the Field Name is limited to ten characters. If you r
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 190 > C1/6 C3/<D><A>SITE<20>1 DATA OUTPUT MENU (
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 191 If you need ARGOS binary data, use Field Type Code #13. If yo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 12Sensor Record #1 is the first sensor in the configuration, Sensor Re
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 192Type of Data Specified In Line Item #4 Recommended Value to Set In
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 193Line Item #7 (the Data Storage Class Code) in each Data Output Reco
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 19410.6.7. Creating An Automatic Output Message for CCSAIL Format You
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1953. After the first Data Output Record, create another Data Output
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 1966. Create another Data Output Record after the backspace using Dat
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 197data referred to in Line Item #4 (the Input Record) of the Conditio
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 19810.6.10. Selecting Data To Log & Transmit Via Output Message N
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 199When the Selectable Transmit and Log data field is used, ZENOSOFT®
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 200 OUTPUT MESSAGE TIMING MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 201REMEMBER: the ZENO®-3200 will automatically transmit output message
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 133. TUTORIAL: BASIC ZENO®-3200 OPERATION Coastal Environmental Syst
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 202Sample Duration is set to 29 minutes and 45 seconds, Output Message
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 203Time :10 :15 :20 :25 :30 :35 :40: 45 :50 :55 :00 :05 :10 :15
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 204When you type R{ENTER} in the Zeno Program Menu, the ZENO®-3200 wil
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 20511. ALARM MESSAGES Coastal Environmental Systems ZENO®-3200 User M
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 206You may configure as many as 4 alarm messages in your ZENO®-3200.
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 207The description of this process in Appendix D, Line Item #5 (the Al
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 208 Use Conditional Start and Conditional Stop Data Output Records (
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 209 You can also configure a single output message to be an alarm mess
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 21011.3.1. Selecting The Communications Port To Transmit The Alarm Mes
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 211You must select the same communications port in the Output Message
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 14After you connect your ZENO®-3200 to your computer and apply power (
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 212A GOES transmitter is limited to transmitting self-timed (regularly
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 213REMEMBER: a message to the ARGOS satellite is limited to 32 bytes!
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 21412. ADVANCED ZENO®-3200 CONFIGURATION TOPICS Coastal Environmental
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 215 Figure 12.1. ZENO®-3200 Timing Structure Diagram. 12
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 216The RTOS is analogous to the Microsoft Windows operating system th
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 217Timing is an ever-present parameter that must be taken into account
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 218There are four Sensor Timing Loops. Each Sensor Timing Loop define
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 219It is very important that the time set in the Sensor Timing Loop fo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 220 The Sample Duration Time must be set to a value greater than or e
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 221The time that is required by each sensor to make a measurement must
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 15 01/07/11,14:13:55,23.7,13.8, 01/07/11,14:14:55,23.7,13.8, 01/07/11,
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 222 If you plan to read each sensor N times, then the total time re
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 223If Ttotal is less than the Sample Duration Time, the ZENO®-3200 wil
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 224If User Interface accessibility is periodically disrupted by your c
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 225 SENSOR MENU (Cn/m) Change Item n To Value m (Jn) Jump
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 226Examples of using Line Item #25 include: Only collecting data fr
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 227The ZENO®-3200 will return the floating-point values 15.2, 55.999,
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 228Changing one of these parameters will change the total amount of me
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 229The contents of a Command Line are changed using menu option Cn/m{E
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 230 Hand-edit the downloaded configuration file using a standard tex
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 231Command Category Brief Description FLOAT n LONG n STRING n (l1[,
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 16If you are curious about the data logging capacity of your ZENO®-320
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 232Each string value will be referred to as S1, S2, etc. within the re
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 233 The serial communications port specified in the Sensor Record is a
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 234The checksum Special Value, sCS, may not be referenced before the S
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 235Three types of information can be used in the Format Specifier: Typ
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 236Data Field Description Data Value Field %% Represents character %
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 237Determine exactly what is contained in a sensor's data message
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 238 Troubleshooting the RECEIVE Command Format Specifier Once commun
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 239communications port that supports one or more serial sensors can ca
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 240In operation and properly configured, the primary ZENO®-3200 will r
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 24113. ELECTRICAL CONSIDERATIONS Coastal Environmental Systems ZENO®-
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 17 DATA RETRIEVAL MENU (A) Show Records AFTER Specified Time
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 242 DC offset voltages arise due to large currents flowing through t
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 243 Sensor ground (marked SGND): this ground should be used only for
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 244If the source “low” output is connected to ground (either directly
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 24513.4. THE ZENO®-3200 CPU BOARD The following is a diagram of the Z
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 246Each COM port provides unique communications link access, which is
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 247Pin Rev. A Function Rev. D Function 1 DCD (Data Carrier Detect)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 248The 25 pins have the following functions: Revision A Revision D
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 24913.5.3. Revision A and Revision D, ZENO®-3200 Communication Wiring
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 250Compass Port (J3 on CPU Board) Pin # Description 1 12 V Switched
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 251Connecting To COM3 Where to Connect COM3 Port Type Lines Required
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 18 > f SYSTEM FUNCTIONS MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page A-1A. CONSTANTS, CONVERSIONS & ASCII TABLE Coastal Environmental
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page A-2Physical Properties of Water Property Value Density 1000 kg/m3 Spe
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page A-3 1 cubic yard = 27 cubic feet = 46,656 cubic inches LIQUID VOLUME
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page A-4 1 acre = 4,046.85 sq. meters 1 square mile = 2.59 sq. km PHYS
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page A-5 DEC is the decimal (base 10) value CHR is the actual characte
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page A-6
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-1B. ZENO®-3200 MENU LISTING Coastal Environmental Systems ZENO®-32
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-2USER MENU C COMMUNICATIONS MENU 1 Baud rate for COM 1 2 Baud rat
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-33 Self-Timed Transmission Interval format is 'dd:hh:mm:ss&apo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 19 > c4/2 SYSTEM FUNCTIONS MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-43 Alternative Source Address 4-11 Remote ZENO Address #1 - #8 R
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-5B Display BIT Status Section 7.6 Ex Display Sensor x Error Codes
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-612: COM1, COM2, COM3 13,17,18: COM2, COM3 14: CH10 through CH16 (u
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-77 - Differential 8 - Free-Running Average 9 - Collection 10 -Trend
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-85 - Arithmetic Processes Category 1 - U-V Vectors To Magnitude-Dire
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-94 Input Record Depends on number & type of Sensor & Process
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page B-10
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-1 C. SENSOR CONFIGURATIONS Coastal Environmental Systems ZENO®-3200 Use
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-2 ITEM DATA COMMAND ENTERED Item 1: Field Type code = 9 : Transmit
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-3 ITEM DATA COMMAND ENTERED Item 1: Sensor Type code = 2 (18-bit Sin
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 203.1.3. Understanding & Changing the Sample Interval and Power U
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-4 * When changing resistor values to measure different voltage ranges
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-5 ITEM DATA COMMAND ENTERED Item 1: Field Type code = 9 : Transmit
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-6 PROCESSING MENU ITEM DATA COMMAND ENTERED Item 1: Process Category
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-7 2. 2 - wire sensor Coastal Environmental Systems (CES) suppli
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-8 PROCESS MENU ITEM DATA COMMAND ENTERED Item 1: Process Category code
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-9 6. HYGROMETRICS 10205H/HT RELATIVE HUMIDITY SENSOR MENU ITEM
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-10 ITEM DATA COMMAND ENTERED Item 1: Field Type code 9 : Transmit
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-11 ITEM DATA COMMAND ENTERED Item 1: Sensor Type code = 3 (18-bit Di
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-12 Settings for Temperature ITEM DATA COMMAND ENTERED Item 1: Field T
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-13 8. SDI-12 SENSOR298 SENSOR MENU Settings for SDI-12 SENSOR on COM2
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 21 Sample Interval |---------------------------------------| 60 sec
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-14 Notes on Connection The SDI-12 data line uses negative logic 0 to 5V
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-15 4.99 k Settings for Temperature ITEM DATA COMMAND ENTERED Item 1:
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-16 10. R.M. YOUNG 05103 WIND MONITOR SENSOR MENU Settings for Wind Dire
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-17 Settings for Wind Direction/Wind Speed ITEM DATA COMMAND ENTERED It
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-18 * Refer to the sensor's manual for correct signal names. 11. EL
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-19 ITEM DATA COMMAND ENTERED Item 1: Sensor Type code = 16 (General
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-20 COMMANDS TO ENTER I1 C1/STRING 4 ( 90, 1, 2, 4 ) I2 C2/FLOAT 9 I3 C3/
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-21 ITEM DATA COMMAND ENTERED Item 1: Process Category Code = 1 : Gen
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-22 Settings for First Cloud Level ITEM DATA COMMAND ENTERED Item 1: F
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-23 12. VAISALA300 425AH OR 425AHW ANEMOMETER The Vaisala 425AH anemomet
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page i Table of Contents TABLE OF CONTENTS ...
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 22Hour of the Day 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-24 ITEM DATA COMMAND ENTERED Item 1: Sensor Type code = 16 (General
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-25 COMMANDS TO ENTER I1 C1/STRING 1 ( 50 ) I2 C2/SEND "\B " I3
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-26 ITEM DATA COMMAND ENTERED Item 1: Process Category Code = 5 : Ari
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page C-27 Settings to Collect Data From Vaisala 425AH Sensor on COM2, Average
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-1 D. ZENO®-3200 PROCESS LIBRARY Coastal Environmental Systems ZENO®-320
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-2 The Averaging Process calculates the average of the data referenced in
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-3 The Running Average will not contain an average specified by the Runn
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-4 Since Bad Sensor Values (BSVs) are NOT processed313, they are NOT ent
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-5 Each block contains the sum total (Tblock) of the values that were rea
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 23 Going to the Data Retrieval Menu (type U{ENTER} D{ENTER}), and lo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-6 1.6. Rate of Change Process Inputs: 4 Any sensor or process output
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-7 1.8. Free-Running Average Process Inputs: 4 Any sensor or process o
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-8 1.10. Trend Data Process Inputs: 4 Any sensor, process or constant
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-9 Assumptions: Null inputs are not processed The Multiple Input Minimum
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-10 Assumptions: None When the control data is 0, the Validated Data outp
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-11 xyusxvsyiiiiiiiiiisin ;cos ;;; giving xi and yi, the unit vecto
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-12 2211211NNiiNiiN, with i defined such that each
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-13 15 Wind Direction during Running Maximum Wind Gust Speed 16 Run
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-14 Assumptions: This process assumes that the wind direction will not c
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-15 When the vehicle is stationary, the True Wind Vector Average Process
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 2412. How much and how often do I want the ZENO®-3200 to perform the c
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-16 2.6. Rainfall Process Inputs: 4 Rain Data 5 Rain accumulation in
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-17 Divide the number of required running intervals by 7 and round it
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-18 The algorithm is that in “Principles of Meteorological Analysis”, by
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-19 Calculating the wet-bulb temperature (TW) begins with the following e
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-20 13 Longitude of the standard time zone meridian 14 Radiation senso
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-21 a long-wave emissivity of the atmospheres long-wave surface emis
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-22 aTe108 1100Pa2016.exp , (5) where the air tempe
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-23 The canopy resistance is set to 70 sm-1. During the night, the canopy
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-24 TTaTTTa**;*Jkg;Jkg K ;46143112.501 102.37 10
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-25 If a NULL compass is defined, the value of Add Compass To Vane has no
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 25ZENO®-3200 Configuration Recipe Card 1. Configure the sensors. 2. Co
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-26 Variable Definition AS Altimeter Setting PV Lowest Valid Pressure T
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-27 The following variables are used by this process: Variable Descripti
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-28 5 Peak Wind Speed Alert Flag 6 Data Invalid Flag E1 Proces
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-29 1. Two running averages are calculated--all the winds to the "l
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-30 Unless otherwise stated, digital outputs are set high or low only whe
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-31 3.2. Data Range Process Inputs: 4 Any sensor or process output 5
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-32 Assumptions: If the Alarm Reset value is less than the Alarm Set-poi
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-33 This process is used to acknowledge (set to low) an alarm set by eith
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-34 Value Referenced in Line Item #4 of Two-Range Alarm Value Referenced
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-35 The Missing Sensor Data Process allows the setting of an alarm condit
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 26 Enter Administrator Password: **** Waiting for all data acquisitio
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-36 defined, the digital outputs and switched voltage are set high and an
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-37 Assumptions: May be used for a weighed bucket rain sensor The Increm
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-38 The Error Checking Alarm Process is an excellent tool for discovering
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-39 The One-shot Daily Timed Event Process is similar to the Timed Event
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-40 E1 Process Error Code Assumptions: Sensor data is scaled to show
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-41 Assumptions: This process is intended for the Paroscientific baromet
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-42 Thermocouple Type Lowest Valid Voltage (µV) First Midrange Voltage (µ
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-43 All immediate temperatures calculated by this process are averaged to
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-44 6 Thermopile output (any sensor, process or constant output) 7
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-45 E1 Process Error Code Assumptions: None This process takes the squ
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 27A Process Record can refer to any Sensor Record or any preceding Pro
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-46 5.7. Divide Two Data Values Process Inputs: 4 Dividend (D) 5 Divisor
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-47 5.13. Conditional Select Process Inputs: 4 Control Data C (D) 5
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page D-48 6. OUTPUT AND CONTROL PROCESSES CATEGORY 6.1. DAC Analog Output Pro
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page E-1E. CONFIGURATION FILE CONTENTS Coastal Environmental Systems ZENO®-320
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page E-22. CONTENTS OF RUN-TIME PARAMETER LINES For interested users, the foll
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page E-3- Output message #2 COM port The line beginning PARAM4 contains the
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page E-4- ARGOS checksum flag - Response delay time - Daylight savings time
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page E-5- BIT name #10 - BIT name #11 - BIT name #12 - BIT name #13 - BIT
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-1F. LIBRARY OF CCSAIL COMMANDS Coastal Environmental Systems ZENO®-3200
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 28 ZENO PROGRAM MENU (S) Sensor Menu (M) Memor
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-2 Requires Requires CCSAIL Command Active CTS Halted Data Col. A
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-3This command is returned from either HOST or the REMOTE to indicate a n
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-4Global or addressed time set command. No message is returned from the
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-5To ID 0134 from 0001, send all data collected since last D@nn or DX@nn
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-6DLnn, DXLnn, Request the latest, most recent nn data sets stored in dat
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-7Request nn unmarked data sets. This command behaves similarly to option
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-86. DIGITAL OUTPUT CONTROL COMMANDS SDOxyy, This command instructs the
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-9This CCSAIL command instructs the ZENO®-3200 to immediately reboot. Th
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-10ZENO®-3200 number 134 to change the sample period to 30 seconds would
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-11If the user attempts to change any of these parameters while the ZENO®
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 29 > H1 * Select Sensor Type Code, valid codes are - 0 (No
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-12ZENOSOFT® will respond with a CCSAIL ERROR 6 if ASCII parameter nnn is
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-13This CCSAIL command will set the floating-point value of all constants
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-14 GETREPEATnnn, Retrieve the value of the nnnth eight remote addresses
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-15#12340001ENDSAMPLE60^C The ZENO®-3200 would respond with: #00011234OK,
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-16ERROR14,29^C 10.5. Create Default Configuration DEFAULTCONFIG This
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-17If script number nnn does not exist, ZENOSOFT® will respond with a CCS
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-18SETGSInnn,mmm,abcde, Change line number mmm in script number nnn to co
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-19#12670001STARTSAMPLE49^C #00011267OK,99^C GETGSInnn, This command ins
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-20placed after record number mmm. If n is B, the new record is placed b
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-21#00015310ERROR61,56^C #53100001SETDATA14,9 1 "AWSPD" P1.11 1
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 30As you can see, the value for Line Item #1 (the Sensor Type Code) ha
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page F-22When the sensor, process or data output records are deleted, any subse
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-1G. INDEX Coastal Environmental Systems ZENO®-3200 User Manual { {{{{{
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-2Alarm Process, 183, 209, 210, D-31, D-32, D-33, D-34, D-37, D-38, D-39
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-3BIT, 18, 19, 60, 62, 70, 73, 119, 120, 134, 136, 138, 139, 166, 200, 20
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-4COM3 Baud Rate, 78 COM3 Port Type, 78 comma delimited, 14, 17, 18, 60,
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-5Data Rounding Process, D-48 Data Storage Class Code, 48, 49, 50, 51, 18
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-6FAA SAWS Wind Gust Process, D-26, D-28 FAA Wind Data Transmit Only, 190
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-7Hygrometrics 10205H/HT Relative Humidity, C-9 I IDC MOM14400, 85 Immedi
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-8modify a configuration, 149 MOnitoring Raw or Scaled Sensor Data, 134 m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-9Permittivity Constant, A-1 Pi, A-1 PIR Temperature Correction, 179, D-4
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 31> C2/IntTemp SENSOR MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-10Real Time Output Format, 18, 19, 60, 62, 66, 70, 73, 197, 198, 199, 20
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-11Sensor Baud Rate, 163, 228, B-6, C-19, C-24 Sensor Bits Per Character,
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-12Speed of Light, A-1 Speed Over Ground, 159 standard deviation, 42, 136
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-13TXA, 79, 97, 251 U UART, 76 u-component, D-13 UDP, 92, 93 unauthorized
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page G-14Wind Vector Average, 74, 179, B-7, C-17, C-26, D-10, D-12, D-13, D-14,
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page ii 4.4.2. Real Time Data Output Message Format...
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 32No exterior physical connections are required to measure the Interna
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 33 > C3/INT SENSOR MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 34> C12/2 SENSOR MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 35 > A SENSOR MENU (Cn/m) Change Item n To Value m (Jn
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 36 > C1/1 C2/Battery C3/BATT C12/2 SENSOR MENU (Cn/m) Change Item
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 373.2.4. Learning How To Configure A Process From the Zeno Program Me
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 38To aid in identifying the type of process desired, each numerical Pr
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 39Since the Process Category in Line Item #1 is already set to 1, it d
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 40 > C3/AvgTemp PROCESS MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 41 > C4/S1 PROCESS MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page iii 6.8.1. Applying To Use ARGOS ...
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 42Error Code.40 You can view the available outputs of any Process Rec
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 43Since you have reached another milestone during the configuration pr
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 44 > H1 * Select Field Type Code, valid codes are - 0 (NUL
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 45 > C1/6 DATA OUTPUT MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 46 > C3/<D><A> DATA OUTPUT MENU (Cn/m) Change Item n T
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 47Type the command string A C1/9{ENTER} in the Data Output Menu to cre
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 48Line item #7 specifies the Data Storage Class Code. If we type H7{E
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 49You now need to set up the last Data Output Record to log and transm
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 50Your screen should look the following: > C3/AvgBatt C4/P2.1 DAT
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 514. RETRIEVING LOGGED DATA Coastal Environmental Systems ZENO®-32
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page iv 10.4.2. User-Defined Process Name...
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 52If you need to adjust the internal ZENO®-3200 clock backward, to avo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 53The content of each Data Record is defined in the Data Output Menu.5
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 54You would type the command L5{ENTER} in the Data Retrieval Menu and
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 55NOTE: The M command will work regardless of when the last @n comman
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 56 DD is the day (1 to 31) HH is the hour of day (00 to 23) MM
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 57The X-modem protocol should be used on any communications interface
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 58In this particular case, the total amount of memory for data logging
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 59 SYSTEM FUNCTIONS MENU (Cn/m) Change Item n To Value m
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 604.4.2. Real Time Data Output Message Format Real time output messag
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 61-1,000,000 is referred to as the Bad Sensor Value. If you do not wan
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page v 13. ELECTRICAL CONSIDERATIONS ...
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 62Coastal Environmental Systems’ PC application, Intercept™ uses the C
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 63The Destination and Source Addresses must each be four characters in
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 64The ZENO®-3200 only responds to a validated CCSAIL message. The res
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 65Destination Address = 1025 Source Address = 0100 Command =
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 66Coastal Environmental Systems' PC application Intercept™ expect
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 67Difference Internal connection. Connected directly to the CPU via 32
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 684.7.2. Retrieving Flash Logging Memory Status If you want to retrie
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 695. INTERNAL ZENO®-3200 SETTINGS Coastal Environmental Systems ZENO
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 705.1. ZENO®-3200 SYSTEM DATE AND TIME Option S in the System Functio
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 71Temperature Sensor is also used to know when the internal temperatur
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page vi Acknowledgements The author, Michael J. Hart, personally thanks each of
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 72The Primary Unit ID is the unique identification number that can be
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 73The Secondary Unit ID is a unique identification number that can be
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 746. COMMUNICATION INTERFACES Coastal Environmental Systems ZENO®-3
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 75After connecting and powering up the ZENO®-3200 as described in Sect
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 76The Communications Menu lets you change the communications settings
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 77The following table summarizes the available settings for each commu
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 78In half-duplex mode, when data are being dumped from the Data Output
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 796.2. DIRECT TERMINAL ACCESS The following is the schematic of the Z
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 80The ZENO®-3200 does not actively assert/de-assert RTS. Instead, the
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 81 USER MENU (C) Communications Menu (T) Test Menu (F)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 11. INTRODUCTION Coastal Environmental Systems ZENO®-3200 User Manua
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 82 MODEM MENU (Cn/m) Change Item n To Value m (Q) Quit (E)
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 83 A modem connection to COM3 has been specified in the Modem Menu but
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 84the correct cable (typically the manufacturer’s modem cable). If yo
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 85*WARNING: If you wish the ZENO®-3200 to dial out, DIP switch #3 must
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 86We also recommend that you force the baud rate between the two modem
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 87Echo Off Normally, a modem echoes all commands it receives. for exa
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 88ZENO COM3 DE-9F MODEM DE-9F shield DCD 1 1 DCD RXD 2 2 RXD
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 89connect and communicate at 4800 BPS. This can be accomplished in tw
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 90Cellular Modem Type Manufacturer AMPS StarComm Cellular Modem 1442E
ZENO®-3200 USER MANUAL Coastal Environmental Systems (206) 682-6048 Page 912. Device Type: Your cellular provider may ask you to identify the