ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048
Page 33
> C3/INT
SENSOR MENU
(Cn/m) Change Item n To Value m (Jn) Jump To Record n
(A) Insert After This Record (N) Go To Next Record
(B) Insert Before This Record (P) Go To Previous Record
(X) Cut Record to Clipboard (XA) Delete ALL Records
(C) Copy Record To Clipboard (Z) Zeno Program Menu
(V) Paste Record From Clipboard (H) Help
(Sn/m) Search Item n for Value m
Sensor Items for Record 1 of 1:
Item 1: Sensor Type Code 1 (12-bit Analog to Digital)
Item 2: Sensor Name IntTemp
Item 3: Sensor Input Channel INTERNAL TEMPERATURE SENSOR
Item 6: Switched Power Code 0 (NO SWITCHED POWER)
Item 7: Sensor Excitation Voltage Code 0 (NO EXCITATION VOLTAGE)
Item 8: Switched Excitation Return 0
Item 9: Switched Power Warmup Time 0
Item 10: Sensor Sample Count 1
Item 11: Maximum Sensor Readings 0
Item 12: Sensor Timing Loop 1 (0.5 seconds)
Item 13: Conversion Coefficient A 0
Item 14: Conversion Coefficient B 1
Item 15: Conversion Coefficient C 0
Item 17: No. of Additional 15-msec Delays 0
>
You have successfully instructed the ZENO
®
-3200 to collect data from the Internal Temperature Sensor
in Sensor Record #1. One more Line Item needs to be examined in the Sensor Menu: Line Item 12, the
Sensor Timing Loop. In our example, we want to collect data from the Internal Temperature Sensor once
a second.
The Sensor Timing Loop tells ZENOSOFT
®
how frequently to collect data
from the defined sensor over the course of the Sample Duration.
The current setting for Line Item #12, the Sensor Timing Loop, is for Timing Loop #1.
There are four available Sensor Timing Loops. Sensor Timing Loop #1 is
always a 0.5-second timing loop, but the other three can be modified using a
different menu.
31
If we keep the Sensor Timing Loop set to 0.5 seconds, ZENOSOFT
®
will read from this sensor every
half-second instead of once per second. The default value for Sensor Timing Loop #2 is 1 second. Type
the command C12/2{ENTER} in the Sensor Menu, and your screen should look something like this:
31
Modifying Sensor Timing Loops is discussed in Section 10.3.7.