ZENO
®
-3200 USER MANUAL
Coastal Environmental Systems (206) 682-6048
Page 223
If T
total
is less than the Sample Duration Time, the ZENO
®
-3200 will NOT
be able to collect data from all of the Sensor Records at the rates specified
by the Sensor Timing Loops. Instead, the Sensor Records will be read less
frequently than specified and with fewer collections than expected.
To correct this unwanted situation, you must (1) reduce the number of times
that you want to collect data from one or more Sensor Records, or (2)
increase the available time in the Sample Duration.
258
To reduce the number of times you want to collect data from a Sensor
Record, you can increase the time of its Sensor Timing Loop.
259
Another
possibility is to set the Maximum Sensor Readings to a value less than the
possible number of times that the Sensor Record can be read during the
Sample Duration.
260
12.1.9. Timing and Effects Upon The User Interface
A very busy, complex configuration contained in the ZENO
®
-3200 may
periodically disrupt accessibility to the User Interface. This includes both
the User Interface Menus and CCSAIL commands.
As stated in Section 12.1.4, ZENOSOFT
®
is a multitasking software application and the ZENO
®
-3200
contains a single CPU. Since Data Collection Task has a higher priority than the User Interface Task, the
RTOS will devote more time to the Data Collection Task than the User Interface Task.
258
Refer to Section 10.3.7.
259
Refer to Section 10.3.7.
260
Refer to Section 10.3.8.