data referred to in Line Item #4 (the Input Record) of the Conditional Start
Data Output Record is not zero.
NO data is transmitted by the Conditional Start Data Output Record itself!
The ZENO
®
-3200 ALWAYS LOGS data from any Data Output Records that
log data and are contained between Conditional Start and Conditional Stop
Data Output Records, regardless of the Conditional Start status!
When you configure a Data Output Record to be a Conditional Start, you will see something like the
following example on your terminal emulation program screen, along with the matching Conditional Stop
Data Output Record.
DATA OUTPUT MENU
(Cn/m) Change Item n To Value m (Jn) Jump To Record n
(A) Insert After This Record (N) Go To Next Record
(B) Insert Before This Record (P) Go To Previous Record
(X) Cut Record to Clipboard (XA) Delete ALL Records
(C) Copy Record To Clipboard (Z) Zeno Program Menu
(V) Paste Record From Clipboard (H) Help
(Sn/m) Search Item n for Value m
Data Items for Record 8 of 72:
Item 1: Field Type Code 10 : Conditional Start Field
Item 2: Output Message(s) 2
Item 3: Field Name BITdisplay
Item 4: Input Record P14.L1 : BIT
> S1/11
DATA OUTPUT MENU
(Cn/m) Change Item n To Value m (Jn) Jump To Record n
(A) Insert After This Record (N) Go To Next Record
(B) Insert Before This Record (P) Go To Previous Record
(X) Cut Record to Clipboard (XA) Delete ALL Records
(C) Copy Record To Clipboard (Z) Zeno Program Menu
(V) Paste Record From Clipboard (H) Help
(Sn/m) Search Item n for Value m
Data Items for Record 11 of 72:
Item 1: Field Type Code 11 : Conditional Stop Field
Item 2: Output Message(s) 2
>
In the above example, Data Output Records #9 and #10 will be transmitted when the value referenced in
Line Item #4 of Data Output Record #8 is not zero.