Appendix B. NL100 TcpServer to RF400 to CR510PB-Router/RF400 to 20 CR205s Network
B-2
LoggerNet Schedule Tab
Collection Interval – 60 minutes
Primary Retry Intervals – 20 minutes
Number of Primary Retries – 2
Secondary Retry Interval – 240 minutes
NL100 Configuration Menu Settings
(Any NL100 options not shown above are disabled).
A PakBus Address is required by setup even though not used.
RF400 Settings
In a PakBus rf network all radios must have the same radio and network
addresses and hopping sequence setting. Addressing is accomplished using the
unique PakBus addresses assigned to the PakBus devices (dataloggers).
1. Configure both RF400 radios with the same Radio Address, Net Address,
and Hopping Sequence. If there will be no other RF400s within range, you
can use default settings.
2. RF400 connected to NL100
Active Interface = “AutoSense”
Standby Mode = “< 24 mA always on”
3. RF400 connected to CR510
Active Interface = CSDC 7 (7 is default but you could configure 8)
Standby Mode = < 24 mA