Appendix H. Adding Direct or P190 Router to RF400 Network
H-2
Antenna Height and Location
• Arrange the router antenna’s height and/or position so that it has a good
‘view’ of the antennas of both the ‘toward LoggerNet’ and the ‘toward
destination’ stations (height is everything in rf links).
CR10XPB_2
|
RF400 Series
CSDC 7
CR205_3
CR205_4
ROUTER
PC
(LoggerNet)
|
RF400 Series
AutoSense
CR510PB_1
|
RF400 Series
CSDC 7
ADDED
Case 2 – P190 Transfers to/from CR205s
This amounts to keeping the P190 address normal but configuring the P190
datalogger’s neighbor filter to discover the router and configuring the router’s
neighbor filter to discover the remote CR205. Refer to illustration below during
setup.
Master Program
• Configure P190 to address destination (CR205_3) by entering “3” in
Parameter 2.
Existing Master Datalogger Configuration
• Create neighbor filter in CR10XPB_1 listing added router CR510PB_2 as
a potential neighbor.
• Make sure that CR205_3 is NOT in the neighbor filter potential neighbor
list.
• Configure CR10XPB_1 as a router in *D15 with PakBus Address (1), max
nodes = 5, max neighbors = 3, max routers = 3 (includes LoggerNet).
Added Router Datalogger Configuration
• Configure CR510PB_2 with neighbor filter listing CR205_3 as a potential
neighbor.
• Configure CR510PB_2 neighbor filter listing CR10XPB_1 as a potential
neighbor.
• In neighbor filter, select datalogger port CSDC 7 (code 17) to hello
potential neighbor.
• Configure CR510_2 as a router in *D15 with PakBus Address (2), max
nodes = 5, max neighbors = 2, max routers = 3 (includes LoggerNet).