AM16/32B Relay Analog Multiplexer
FIGURE 1. AM16/32B Relay Multiplexer
3. AM16/32B Specifications
Power
*
:
Unregulated 12 VDC
Minimum Operating Voltage:
from –55C to +40C = 11.3 VDC;
from +40C to +85C = 11.8 VDC
(See Figure 2 for relay actuation times vs.
temperature and supply voltage.)
Current Drain:
Quiescent: < 210 uA
Active: 6 mA typical in “2 x 32” mode
11 mA typical in “4 x 16” mode
Reset
*
:
A continuous signal between 3.3 VDC and 8 VDC
holds the AM16/32B in an active state (where a
clock pulse can trigger a channel advance). A
signal voltage < 0.9VDC deactivates the
AM16/32B (clock pulse will not trigger a scan
advance; AM16/32B is also reset).
Clock
*
:
On the transition from <1.5 V to >3.3 V, a scan
advance is actuated on the leading edge of the clock
signal; clock pulse should be a minimum of 1 ms
wide; maximum voltage is 8 VDC.
Operational
Temperature:
Standard: -25
o
C to +50
o
C
Extended: -55
o
C to +85
o
C
Operational
Humidity:
0 - 95%, non-condensing
Dimensions:
Length – 23.9 cm (9.4")
Width - 10.2 cm (4.0")
Depth - 4.6 cm (1.8")