AM16/32B Relay Analog Multiplexer
4.2.1 COM Terminals
A CABLE3CBL, CABLE4CBL, MUXSIGNAL, or CABLE5CBL cable is
used to connect the datalogger to the COM terminals. The CABLE3CBL is
recommended when the AM16/32B is used in the 4x16 mode. Either the
CABLE4CBL or MUXSIGNAL is typically used for the 4x16 mode. The
CABLE5CBL is recommended for the 4x16 mode when it is desirable to
connect both shields.
The four terminals dedicated to multiplexer-datalogger connection are located
under the blue “COM” next to the mode switch. The terminals are labeled:
ODD H, ODD L, EVEN H, and EVEN L. In “4x16” mode the AM16/32B
maintains the four “COM” terminals electrically isolated from one another. In
“2x32” mode the AM16/32B maintains an internal connection between ODD
H and EVEN H and between ODD L and EVEN L.
Common “
” terminals are provided next to the COM ODD and COM EVEN
terminals. They bus internally to the other thirty-two “
” terminals on the
AM16/32B and are connected at all times (i.e., not switched). Their function is
to provide a path to ground for sensor cable shields. A “COM
” terminal
should be wired to datalogger ground via the cable’s shield according to the
following table.
COM
ODD
4X16
HL
EVEN
HL
O
N
MUXSIGNAL
SHIELD
CR10X
CR23X
CR1000
CR3000,
CR5000
21X
CR7
CR800,
CR850
G
E1-E3 EX1-EX4 EX1-EX3 or
VX1-VX3
VX1-VX4 EXCITATION SWITCHED
ANALOG OUT
EX1-EX2 or
VX1-VX2
SE3 SE3 SE3 SE3 2H 2H SE3
SE2 SE2 SE2 SE2 1L 1L SE2
SE1 SE1 SE1 SE1 1H 1H SE1
CABLE
FIGURE 6. Typical AM16/32B to Datalogger Signal Hookup (4x16 Mode)
using CABLE4CBL or MUXSIGNAL Cable
4.2.2 Sensor Input Terminals
The terminals for sensor attachment are divided into 16 groups (panel switch
set to “4x16”) or into 32 groups (panel switch set to “2x32”). The groups
consist of four or two Simultaneously Enabled Terminals (SETs). With panel
switch set to “4x16” mode the blue channel numbers apply. The SETs are
numbered starting at 1 (1H, 1L, 2H, 2L) and continuing until SET 16 (31H,
31L, 32H, 32L).
In “4x16” mode the odd numbered terminals (example: 5H, 5L) are relay
switched to the COM ODD terminals while the even terminals (6H, 6L) are
switched to the COM EVEN terminals. When activated by the RES line being
high, as the AM16/32B receives clock pulses from the datalogger, each SET of
11