AM16/32B Relay Analog Multiplexer
21
GENERALIZED “4x16” MODE PROGRAM LOOPS FOR THE CR23X, CR10(X), 21X, and CR7
21X SAMPLE PROGRAM
* 1 Table 1
Programs
01: 60 Sec.
Execution
Interval
:ACTIVATE MULTIPLEXER
1: Set Port (P20)
1: 1 Set high
2: 1 Port
Number
:BEGIN MEASUREMENT
;LOOP
2: Beginning of Loop (P87)
1: 0 Delay
2: 16 Loop Count
;CLOCK PULSE AND DELAY
3: Excitation with Delay (P22)
1: 1 EX Chan
2: 1 Delay w/EX
(units=.01
sec)
3: 1 Delay after
EX (units=
.01 sec)
4: 5000 mV
Excitation
4: User Specified Measurement
Instruction
;END MEASUREMENT
;LOOP
5: End (P95)
;DEACTIVATE
;MULTIPLEXER
6: Set Port (P20)
1: 0 Set low
2: 1 Port
Number
CR7 SAMPLE PROGRAM
* 1 Table 1
Programs
01: 60 Sec.
Execution
Interval
;ACTIVATE MULTIPLEXER
1: Set Port (P20)
1: 1 Set high
2: 1 EX Card
3: 1 Port No.
;BEGIN MEASUREMENT
;LOOP
2: Beginning of Loop (P87)
1: 0 Delay
2: 16 Loop Count
;CLOCK PULSE AND DELAY
3: Excitation with Delay (P22)
1: 1 EX Card
2: 2 EX Chan
3: 1 Delay w/EX
(units=.01
sec)
4: 1 Delay after
EX (units =
.01 sec)
5: 5000 mV
Excitation
4: User Specified Measurement
Instruction
;END MEASUREMENT
;LOOP
5: End (P95)
;DEACTIVATE
;MULTIPLEXER
6: Set Port (P20)
1: 0 Set low
2: 1 EX Card
3: 1 Port No.
CR10X, CR23X SAMPLE PGM
* 1 Table 1
Programs
01: 60 Sec.
Execution
Interval
;ACTIVATE MULTIPLEXER
1: Do (P86)
1: 41 Set high
Port 1
;BEGIN MEASUREMENT
;LOOP
2: Beginning of Loop (P87)
1: 0 Delay
2: 16 Loop Count
;CLOCK PULSE
3: Do (P86)
1: 72 Pulse Port
2
;DELAY
4: Excitation with Delay (P22)
1: 1 EX Chan
2: 0 Delay w/EX
3: 1 Delay after EX
4: 0 mV
Excitation
5: User Specified Measurement
Instruction
;END MEASUREMENT
;LOOP
6: End (P95)
;DEACTIVATE
;MULTIPLEXER
7: Do (P86)
01: 51 Set low
Port 1
FIGURE 8. Example “4x16” Mode Program Loops for CR23X, CR10(X), 21X and CR7 Loggers