SECTION 7. MEASUREMENT PROGRAMMING EXAMPLES
7-2
;Measure Relative Humidity.
;
04: Volts (SE) (P1)
1: 1 Reps
2: 25 ±5000 mV Slow 60 Hz
Rejection Range
3: 6 SE Channel
4: 2 Loc [ RH_pct ]
5: .1 Mult
6: 0 Offset
;Turn CS500 off.
;
05: Do (P86)
1: 59 Set Switched 12 V Low
INPUT LOCATIONS
1 Temp_C
2 RH_pct
Temperature (Black)
Relative Humidity (Brown)
12 V (Red)
Power Ground (Green)
Shield (Clear)
CS500
SE 5
SE 6
SWITCHED 12V
G
CR23X
FIGURE 7.1-1. Wiring Diagram for CS500
CR23X
FIGURE 7.1-2. Typical Connection for Active Sensor with External Battery