Section 15. Alternate Telecoms Resource Library
Table 20. CRBASIC Ports, Flags, Variables and Modbus Registers
CR200(X) Feature
Example CRBASIC
Declaration
Equivalent Example
Modbus Register
Control Port (Port) Public Port(8) 00001 to 00009
Flag Public Flag(17) 00001 to 00018
Boolean Variable Public ArrayB(56) as Boolean 00001 to 00057
Variable Public ArrayV(20)*
40001 to 40041*
or
30001 to 30041*
*Because of byte number differences, each CR200(X) domain variable translates to two Modbus domain input / holding
registers.
15.1.3.2 CRBASIC Instructions - Modbus
Complete descriptions and options of commands are available in CRBASIC
Editor Help.
ModbusMaster ()
Sets up a CR200(X) as a Modbus master to send or retrieve data from a Modbus
slave.
Syntax
ModbusMaster (ResultCode, ComPort, BaudRate,
ModbusAddr, Function, Variable, Start, Length,
Tries, TimeOut)
ModbusSlave ()
Sets up a CR200(X) as a Modbus slave device.
Syntax
ModbusSlave (ComPort, BaudRate, ModbusAddr,
DataVariable, BooleanVariable)
15.1.3.3 Addressing (ModbusAddr)
Modbus devices have a unique address in each network. Addresses range from 1
to 247. Address 0 is reserved for universal broadcasts. When using the NL100,
use the same number as the Modbus and PakBus® address.
15.1.3.4 Supported Function Codes (Function)
Modbus protocol has many function codes. CR200(X) commands support the
following.
01 Read Coil Status
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
141