Section 14. PakBus Networking
14-3
Neighbor Filter Using Device Configuration Utility, Settings Editor, type into Neighbors
Allowed SDC7 “(20, 20)” [Enter] and into Verify Interval SDC7 “60”
[Enter]. This will configure a neighbor filter seeking/allowing PakBus
address 20 as a neighbor with a verification interval of 60 seconds.
Remember to Apply settings.
Router Using Device Configuration Utility, Settings Editor, configure CR800_10
as a router by making Is Router equal to “1”.
Central Routers Not needed. Leave them at zero (or blank).
Beaconing Leave Beacon Intervals on all ports at zero.
Baud Rate SDC7 Not user configurable (see Network Configuration Basics, Communication
Peripheral Setup, Baud Rates).
Example Network – CR800_20 Configuration (Leaf-Node)
Setup Description
General If CR800 settings have changed from factory defaults, use Device
Configuration Utility to set factory defaults, and then proceed with setups
below.
PakBus Address Using Device Configuration Utility, make CR800’s PBA the same as in
LoggerNet map:
Neighbor Filter No neighbor filter required. (CR800_10 will neighbor filter discover
CR800_20.)
Router Leave IsRouter at the default setting of “False” or zero.