HC2S3 Temperature and Relative Humidity Probe
6
6.1 Temperature Sensor
Sensor: PT100 RTD, IEC 751 1/3 Class B, with calibrated signal conditioning
Temperature Measurement Range: -50°C to +100°C (default -40°C to + 60°C)
Temperature Output Signal Range: 0 to 1.0 V
Accuracy at 23°C: ±0.1°C with standard configuration settings
Long Term Stability: <0.1°C/year
Sensor Time Constant (63% step change (1 m/sec air flow at sensor)): 22 sec
with PE filter, 30 sec with Teflon filter
Temperature Accuracy over Temperature:
6.2 Relative Humidity Sensor
Sensor: ROTRONIC Hygromer
®
IN1
Relative Humidity Measurement Range: 0 to 100% non-condensing
RH Output Signal Range: 0 to 1 VDC
Accuracy at 23°C
±0.8% RH with standard configuration settings
Typical Long Term Stability: <1% RH per year
Sensor Time Constant (63% of a 35 to 80% RH step change (1 m/sec air flow at
sensor)): 22 sec with PE filter, 30 sec with Teflon filter