cR500
6.12 Troubleshooting
No Response
From
Datalogger
Using
CRl OKD
c.
Make sure
the battery has been installed, and
the
power
"oN".
Use
a
voltmeter
to measure the voltage
on the
12 V
and G
terminals on
the datalogger; the voltage must be between 9
and 16 VDC.
Disconnect
any sensor or
peripheral
wires connected
to
the
and 12 V terminals.
D. Disconnect
any communications or storage
peripherals
datalogger;--.*
E.
Reset
the datalogger by
turning the
power
switch to
"OFF",
to
"ON".
F. lf still no response,
callCampbell Scientific.
24