SPECIFICATIONS
A.1 General
Power Requirements: 10-16 VDC (unregulated)
Quiescent Current (MICRO-800/MICRO-1000 mode): 80 µA (16CH mode)
130µA (32CH mode)
Quiescent Current (GK-403 mode): 12 mA
Channel Activated Current: 30 mA
Control Line Input Impedance: 100 kΩ (CLOCK), 100 kΩ (RESET)
Control Line Input Levels: TTL or RS-232 (±9 VDC)
Transient Protection: 16 VDC Transzorbs
Operating Temperature: −40 to +60° C
A.2 Relays
Type: NAIS TXS2SA-4.5V DPDT non-latching
Power: 11.1 mA @ 5VDC (55.5 mW)
Contact Type: Gold clad silver alloy
On Resistance: 100 mΩ
Coil Resistance: 405 Ω
Maximum Switching Power: 30W (resistive)
Maximum Switching Voltage: 110 VDC
Maximum Switching Current: 1 A
Operate Time: ≈5 msec Max.
Release Time: ≈5 msec
Switching Life: 5 x 10
7
operations (mechanical)
2 x 10
5
operations (electrical @ 30W)
Ambient Temperature: −40 to +70°C
A.3 Tripolar Plasma Surge Arrestor
Nominal DC Breakdown Voltage: 230V
Surge Life: 100 (10/1000 ms pulse @ 200 A)
Maximum Surge Current: 5 kA per side (8/20 µs pulse)
Insulation Resistance: 10
9
Ω
Operating Temperature: −65 to +125° C
A.4 Bipolar Plasma Surge Arrestor
Nominal DC Breakdown Voltage: 150V
Maximum Surge Current: 1 kA (8/20 µs pulse)
Insulation Resistance: 10
10
Ω
Operating Temperature: −65 to +125° C